Kyoritsu 6010B User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
15
63 Preparation for measurement
Before testing, always check the following:-
1. The low battery Indication " " is not displayed
2. There is no visually obvious damage to the tester or to the test leads.
3. Test the continuity of the test leads by switching to continuity test and
shorting out the lead ends. A high reading will indicate that there is a faulty
lead or that the fuse is blown.
4. MAKE SURE THAT THE CIRCUIT TO BE TESTED IS NOT LIVE. A
warning LED is lit if the instrument is connected to a live circuit but test the
circuit as well!
64 Insulation resistance measurement
KEW 6010B has a selectable, double test voltage of 500V and 1000V DC.
1. Select the insulation resistance setting by rotating the function switch to the
required test voltage - "500V" or "1000V" as indicated under the "insulation"
test section of the functional switch, after making sure that the instrument is
not connected to a live circuit.
2. Attach the test leads to the instrument and to the circuit or the appliance
under test. (see Figs 7 & 8)
Note : Insulation testing must only be undertaken on de-energised circuits.
Fig 7
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 35 36

Comments to this Manuals

No comments