KEW 6010B Multi-Function tester performs six functions in one instrument.
1. Continuity tester
2. Insulation resistance tester (500V/1000V)
3. Loop impedance tester
4. RCD tester
5. Uc tester
6. Mains voltage warning when operating the Loop, RCD and Uc mode.
Above test results: item1 through 5, can be saved to the internal memory; and
they can be recalled whenever necessary.
Data can be transferred from KEW6010B to PC by using MODEL8212 and
"KEW Report" (Optional accessory).
The tester is designed to Safety Standard
IEC 61010-1 CAT III (300V) Pollution degree 2, IEC 61557-1, 2, 3, 4, 6, 10.
Drip-proof construction in conformance with IP40, IEC 60529.
The instrument is supplied with:-
1. KAMP10 lead for Loop/RCD/Uc testing at socket outlets.
2. Model 7025 lead for Continuity and Insulation testing.
Continuity and insulation resistance functions have the following features:-
Rated current Continuity: 200mA as required in IEC 61557-4
(Buzzer sounds when test current exceeds 200mA)
Insulation: 1mA as required in IEC 61557-2
Live circuit warning A colour coded LED and buzzer warn if the
circuit under test is live.
Continuity Null Allows automatic subtraction of test lead
resistance from continuity measurements.
Auto discharge Electric charges stored in capacitive circuits
are discharged automatically after testing by
releasing the test button.
Loop impedance, RCD and Uc testing functions have the following features:-
Voltage level Supply voltage is displayed when the
instrument is connected to the supply until the
test button is pressed.