Kyoritsu 6010B User Manual Page 21

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 20
7.4 The loop impedance test
Since the earth fault loop is made up of conducting path which includes the
supply system back to the supply transformer, it follows that loop testing can
only be carried out after the mains supply has been connected. KEW 6010B
takes a current from the supply and measures the difference between the
unloaded and loaded supply voltages. From this difference it is possible to
calculate the loop resistance. In many cases, any RCD in the circuit will be
tripped by this test, which draws current from the phase and returns it through
the earth system. The RCD will see this as the type of fault it is designed to
protect against, and will trip. To prevent this unwanted RCD tripping during loop
testing, any RCD must be taken out of circuit and temporarily replaced with a
suitably rated MCB unit. The RCD will need to be replaced after the loop test is
completed.
WARNING
DO NOT PROCEED WITH TESTING UNLESS THE P-E AND P-N
LEDs ARE LIT TO CONFIRM THAT THE WIRING IS CORRECTLY
CONNECTED. Should these two LEDs not be lit, investigate the
wiring connections of the installation and rectify any faults before
proceeding with the test. If the LED is lit do not proceed.
1.Power on the instrument.
2.Set the function switch to Loop 20Ω range.
3.If testing sockets, connect the plug lead to the KEW 6010B and push the
moulded plug into the socket to be tested (see Fig 11).
4.Check the wiring LEDs are lit (see above).
5.Note the mains voltage displayed by the instrument.
6.Press the test button. The value of the measured loop impedance will be
displayed with the appropriate units.
7.If testing lighting or other circuits, connect the three-wire lead Model 7133
(OMA DIEC :optional accessory) to KEW 6010B, connect the red (phase)
lead to the phase connection of the circuit under test, connect the black
(neutral) lead to the neutral connection of the circuit under test, and connect
the earth lead to the earth associated with the circuit (see Fig 12).
8.If any RCD associated with the circuit trips out, reset the RCD and try
testing again, this time operating the /180°select switch once prior to
pressing the test button. This will change the period of the waveform over
which the instrument performs the loop test. This may result in the RCD not
tripping out.
If the RCD still trips, temporarily replace it with a suitably rated MCB for the
duration of the test.
9.If the instrument measures greater than 20Ω the over-range symbol "OL"
will be displayed. If this is the case, switch the instrument up a range to the
2000Ω range and repeat the test to obtain a satisfactory reading. If the
instrument is set to the Loop 2000Ω range, the test will be carried out at the
reduced current of 15mA flowing. This setting will be very unlikely to trip out
the circuit RCD.
19
Page view 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 35 36

Comments to this Manuals

No comments