Kyoritsu 6010A User Manual Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
4
Model 6010A Multi-Function tester performs five functions in one instrument.
1Continuity tester
2Insulation resistance tester
3Loop impedance tester
4RCD tester
5Mains voltage warning when operating the loop impedance and RCD
mode.
The tester is designed to Safety Standard IEC 61010-1
EN 61010-1 CAT III
(300V).
Dust proof construction in conformance with IP50, IEC529.
The instrument is supplied with:
-
1A KAMP10 lead for loop/RCD testing at socket outlets.
2Model 7025 lead for insulation and continuity testing.
In the insulation resistance testing mode the instrument provides a rated current
of 1mA as required in
IEC 61557-2
EN 61557-2 1997.
In the continuity testing mode the instrument provides a short circuit current of
200mA as required in
IEC 61557-4
EN 61557-4 1997.
Continuity and insulation resistance functions have the following features:-
Live circuit warning A colour coded LED warns if the circuit under
test is live.
Auto discharge Electric charges stored in capacitive circuits
are discharged automatically after testing by
releasing the test button.
Test current Warning Beeper Warns when the test current exceeds
200mA
(IEC 61557-4)during continuity measurement.
Loop impedance and RCD testing functions have the following features:-
Voltage level In the loop impedance mode, supply voltage
is displayed when the instrument is connected
to the supply until the test button is pressed.
Wiring check Three LEDs indicate if the wiring of the circuit
under test is correct.
Page view 5
1 2 3 4 5 6 7 8 9 10 11 ... 31 32