only be carried out after the mains supply has been connected. In many cases,
any RCD in the circuit will be tripped by this test, which draws current from the
phase and returns it through the earth system. The RCD will see this as the
type of fault it is designed to protect against, and will trip. To prevent this
unwanted RCD tripping during loop testing, any RCD must be taken out of
circuit and temporarily replaced with a suitably rated MCB unit. The RCD will
need to be replaced after the loop test is completed.
WARNING
DO NOT PROCEED WITH TESTING UNLESS THE P-E AND P-N
LAMPS ARE LIT TO CONFIRM THAT THE WIRING IS CORRECTLY
CONNECTED. Should these two lamps not be lit, investigate the
wiring connections of the installation and rectify any faults before
proceeding with the test. If the LED is lit do not proceed.
1Press the test button once. Then, the instrument switches on.
2Set the instrument to loop test 20Ωrange.
3If testing sockets, connect the plug lead to the Model 6010A and push the
moulded plug into the socket to be tested (see Fig 9).
4Check the wiring lamps are lit (see above).
5Note the mains voltage displayed by the instrument.
6Press thePress to testbutton. The value of the measured loop
impedance will be displayed with the appropriate units.
7If testing lighting or other circuits, connect the three-wire lead OMA DIEC to
Model 6010A, connect the red (phase) lead to the phase connection of the
circuit under test, connect the black (neutral) lead to the neutral connection
of the circuit under test, and connect the earth lead to the earth associated
with the circuit. (see Fig 10).
8If any RCD associated with the circuit trips out, reset the RCD and try
testing again, this time operating the phase selector switch once prior to
pressing the test button. This will change the period of the waveform over
which the instrument performs the loop test. This may result in the RCD not
tripping out. If the RCD still trips, temporarily replace it with a suitably rated
MCB for the duration of the test.
9If the instrument measures greater than 20Ωthe over-range symbolOL
will be displayed. If this is the case, switch the instrument up a range to the
2000Ωrange and repeat the test to obtain a satisfactory reading. If the
instrument is set to the "loop2000Ω"position,the test will be carried out at