Kyoritsu 3127 User Manual

Browse online or download User Manual for Tools Kyoritsu 3127. KYORITSU 3127 User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - KEW 3127

INSTRUCTION MANUALHIGH VOLTAGE INSULATION TESTERKEW 3127

Page 2 - Contents

- 7 -  <Voltage monitor for insulation resistance range>Rated voltage 250V 500V 1000V 2500V 5000V AccuracyMeasuring range30-330V 30-650V 30-1200

Page 3

- 8 -●Display: Liquid crystal display Bar graph: Max. 41points DAR/PI value: 9.99 Time: 99:59●Low battery warning: Battery mark display (in 4 lev

Page 4 - 1. Safety warnings

- 9 -●Current consumption (representative values at 12V of supply voltage)Range 250V 500V 1000V 2500V 5000V VOLTOutput at short-circuitFor 10 sec afte

Page 5 - # WARNING

- 10 -19181718569427101112131415163204. Instrument layout4-1 Instrument layout 1 LCD display 2 MEMORY button 3 ENTER button 4 MODE button 5 ESC b

Page 6

- 11 -4-2 LCD display 1 Battery mark 2 Overheat warning mark 3 AC/DC mark4 LOGGING mark5 MEMORY mark6 FILTER mark7 Date and time mark8 Time 9 DAR/PI/D

Page 7

- 12 -4-3 Opening and closing Hard caseThe Latching device has two features: the larger portion which is the latch itself ①, and the small latch relea

Page 8 - 2. Feature

- 13 -5. Preparation for measurementIt is recommended to charge the battery with reference to “10.1 How to charge battery” described in the manual bef

Page 9 - 3. Specification

- 14 -6. Measurement6-1 Mains disconnection check (Voltage measurement)# DANGER ● Do not make measurement on a circuit in which the electri

Page 10

- 15 -6-2 Insulation resistance measurement# DANGER ● Confi rm that no electrical charge exists on the circuit under test before measuring

Page 11

- 16 -  To check the insulation of electric equipments or electric circuits, measure their insulation resistances by using this instr

Page 12

Contents1.Safety warnings ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 12.Feature ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・

Page 13 - 4. Instrument layout

- 17 -(3) Connect the Earth cord (black) to the Earth terminal of the circuit under test.(4) Put the tip of the Line probe (red) to the circuit under

Page 14

- 18 -(7) Set the Range switch to “OFF” position, and remove test leads from the instrument.Note)● The voltage warning mark stays on durin

Page 15

- 19 -6-3 About BREAKDOWN mode and BURN modeEither Breakdown mode or Burn mode can be set for each measurement: IRPI/ DAR, SV, DD, RAMP.(1) Breakdown

Page 16 - # DANGER

- 20 -6-4 Continuous measurementPress down and turn the Test button clockwise to lock it to perform a continuous measurement of insula

Page 17 - 6. Measurement

- 21 -6-5 IRPI/DAR MeasurementAt IRPI/DAR measurement, PI/ DAR values are automatically calculated and displayed. During a measurement, v

Page 18

- 22 -(2) Setting procedures  Follow the procedures below[Stand-by state]     ENTER button( )Setting of Measurement duration (with UP/DOWN button ( )

Page 19

- 23 -6-5-2DAR - Dielectric Absorption RatioDAR measurement is almost same to PI measurement in a sense that they test the time course of insulation.

Page 20

- 24 -When DAR/PI values are displayed as“---”:DAR and PI values are determined by the methods 1. and 2. as described above, therefore, they are displ

Page 21

- 25 -6-5-4 How DAR/ PI values are displayedLCD shows DAR/PI values as shown below during measurements.(1) Start of testNo DAR/PI value,“---” is displ

Page 22 - When breakdown occurs

- 26 -6-5-5 How to review the measured DAR/PI valuesPress the UP/DOWN button () when measurements end. The measured results are then displaye

Page 23

8.Clock Setting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・389. Communication Function/ Software ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・39

Page 24 - PI/DAR are as follows

- 27 -6-6 SV Measurement (Step Voltage)This is a test based on the principle that an ideal insulation will produce identical readings at all voltages,

Page 25 - Insulation resistance

- 28 -Setting proceduresFollow the procedures below.[Stand-by state]     ENTER button( ) Setting of Step time (with UP/DOWN button( ))     ENTER butto

Page 26

- 29 -(1) Setting items  Setting items for DD measurement are as follows.  (For DD measurement, 250V cannot be set at 500V (250V) Range.)  * Step t

Page 27

- 30 -6-8 Ramp Measurement Voltage used in Step voltage test is raised in steps but that used in Ramp measurement is gradually raised. T

Page 28

- 31 -(1) Setting items  Setting items for RAMP measurement are as follows.  (For RAMP measurement, 250V cannot be set at 500V (250V) Range.)  * Sp

Page 29 - Return to (1)

- 32 -6-9 Voltage characteristics of measuring terminal6-10 Use of Guard terminalWhen measuring the insulation resistance of a cable, leakage current

Page 30

- 33 -6-11 Filter functionKEW3127 has Filter function. Filter Mode is effective to reduce the variations in readings due to external influences during

Page 31 - Dielectric

- 34 -7. Memory Function7-1 Function DetailsMeasurement data of insulation resistance can be saved in the internal memory of KEW3127.Following data ca

Page 32

- 35 -7-2 How to save dataFollow the procedures below to save the measured data.Pressing the ESC button (), during operation, returns to the previous

Page 33

- 36 -7-3 How to recall saved dataFollow the procedures below to recall the saved data.Pressing the ESC button (), during operation, returns to the pr

Page 34

- 1 -1. Safety warningsThis instrument has been designed, manufactured and tested according to IEC 61010: Safety requirements for Electronic measuring

Page 35 - 250V range

- 37 -7-4 How to delete dataFollow the procedures below to delete the saved data.Pressing the ESC button (), during operation, returns to the previous

Page 36

- 38 -8.Clock SettingFollow the procedures below and adjust the internal clock of KEW3127. To confi rm the clock time, use the PC application “KEW Wind

Page 37 - 7. Memory Function

- 39 -9. Communication Function/ Software9-1 KEW3127 SettingsThe PC software application enables analysis of the saved data from PC. KEW312

Page 38 - “LOGGING”

- 40 -Instrument settingFollow the procedure below and select the communication method on KEW3127 before starting PC communication. (1) Hold down the

Page 39 - (1s or longer)

- 41 -● Interface(1) Bluetooth  Bluetooth Ver2.1+EDR (Class2)  Compliant profi le: SPP(2 )MODEL8212USB  Communication method: USB Ver1.1● Software 

Page 40

- 42 -9-2 How to install the SoftwareFollowings are the instructions to install the software“KEW Windows”and “KEW Windows for KEW3127”.(1) Bef

Page 41 - 8.Clock Setting

- 43 -Enter the user information and specify the location to where install the software. Then click“ Next”. Confirm the information on install, and cli

Page 42

- 44 -Click“ Finish” when install completes.An installation of“KEW Windows for KEW3127”is followed by the installation of“ KEW Windows”.

Page 43

- 45 -● To install the “KEW Windows for KEW3127", you can follow the same installation procedure described for“ KEW Windows”.If you n

Page 45

- 2 -# DANGER● Never make measurement on the circuit in which electrical potential to ground over 600V exists.● Do not attempt to make mea

Page 46 - Then click“ Next”

- 47 -9-4 Features of KEW Smart  Remote checking of measurements is possible without accessing KEW3127 using the special Android application “KEW

Page 47

- 48 -10.Battery Charging and Replacement10-1 How to charge battery# DANGERUse only the Power adapter supplied with this instrument.Connect the Power

Page 48

- 49 -10-2 How to replace battery# DANGER● Never open the battery compartment cover while making measurement. ● To avoid possible electric shock, dis

Page 49

- 50 -(3) Pull up the battery as below and disconnect the red and black cables. (Pull the positive and negative connectors upwards and disconnect the

Page 50

- 51 -11.Accessories11-1 Metal parts for Line Probe, and replacement# DANGERIn the electrical environment of CAT.II or higher, MODEL8255 should be att

Page 51

- 52 -11-2 How to use the adaptor for recorderMODEL8302 is the adaptor for recorder (option) for output current measurement. Connect it as shown in th

Page 52 - # CAUTION

- 53 -12. Disposing the ProductWaste Electrical and Electronic Equipment (WEEE), Directive 2002/96/ECThis Product complies with the WEEE Directive (20

Page 54 - MODEL8254

- 55 -MEMO

Page 56 - 12. Disposing the Product

- 3 -# CAUTION● Always make sure to set the Range switch to the appropriate position before making a measurement.● Set the Range Switch to “OFF

Page 57

13-07 92-2156DISTRIBUTORKyoritsu reserves the rights to change specifications or designs described in this manual without notice and witho

Page 58

- 4 -○ Measurement categories(Over-voltage categories) To ensure safe operation of measuring instruments, IEC 61010 establishes safety standards for

Page 59

- 5 -2. Feature KEW3127 is a microcomputer controlled, high voltage insulation resistance tester with 5-range for measuring insulation resistance.● De

Page 60 - 13-07 92-2156

- 6 -3. Specification● Applicable standards  IEC 61010-1 Measurement CAT. IV 600V Pollution degree2  IEC 61010-031 Standard for hand-held probes